Transformer power (kVA)
10
12.5
15
18
20
25
35
Mains contactor from Siemens
3TF44
3TF46
3TF46
3TF47
3TF47
3TF47
3TF50
Secondary transf. nominal current (A)
25.1
31.4
37.7
45.2
50.3
62.8
88.0
3. Guidelines for installation and electrical connections
3.3. Fuse protection for the power connection
The KDV 2.3 mains connection can be protected by using either circuit
breakers or gL classsification fuses (slow-blow). Using power circuit breakers
has the advantage that faulty operation, with two phases, for example, is not
possible.
The protective device is generally placed on the primary side if a matching
transformer is used.
Figure 3.5: Selecting the mains contactor
Nominal (A)
current
14.5 25.1
18.1 31.4
21.7 37.7
26.0 45.2
28.9 50.3
36.1 62.8
50.6 88.0
Recommended
fuses of the
gL type
20 A slow-blow
25 A slow-blow
25 A slow-blow
35 A slow-blow
35 A slow-blow
50 A slow-blow
63 A slow-blow
Siemens power
circuit breaker
3V..
1)
series
3VU1300-•MP00
3VU1600-•MP00
3VU1600-•MP00
3VU1600-•MQ00
3VU1600-•MQ00
3VU1600-•MR00
3VF3111-5DN71
primary second.
Transf.
power
(kVA)
10
12.5
15
18
20
25
35
Setting
range
(A)
18
22
26
32
36
46
60
Setting
range
(A)
18 to 25
22 to 32
22 to 32
28 to 40
28 to 40
36 to 50
40 to 80
Fuses for
3 x AC 400 V mains
voltage
1)
Maximum back-up fuse must be as per manufacturer's guidelines!
Figure 3.4: Fusing with 3 x AC 400 V mains voltage
If an INDRAMAT transformer is used and all connections are executed as
outlined in section 3.2 then fuses and protective circuit breakers with a mains
voltage of 3 x AC 400 V can be used (see table below).
Maximum permissible
fusing
secondary sideprimary side
3 x AC 220 V I
N
= 80 A --- ---
upto 3 x AC 240 V --- I
N
= 80 A I
N
= 80 A
upto 3 x AC 525 V --- I
N
= 63 A I
N
= 80 A
Nominal voltage fuse (gL) / power circuit breakerMains voltage
Figure 3.3: Maximum permissible fusing
3.4. Selecting the mains contactor
The following selection of transformers applies if power is connected on the
secondary side of the mains transformer (as per KDV 2.3 terminal diagram).
The choice must correspond to the nominal current of the secondary side of
the mains transformer. Peak making currents need not be considered because
of the KDV 2.3 charging current limitation.
connected without
matching transformer
connected with matching transformer