Bosch FPC-500-8 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Protection contre les incendies Bosch FPC-500-8. FPC-500 Conventional Fire Panel Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 5
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Fire Alarm Systems | FPC-500 Conventional Fire Panel
FPC-500 Conventional Fire Panel
www.boschsecurity.com
u High-value modern optics – suitable for public
access areas
u Plain text LCD
u Available for 2, 4 or 8 detector zones for up to 64,
128 or 256 detectors
u Optional use of EOL module (EN 54-13 requirement)
u Strong 3 A power supply
The FPC‑500‑x Conventional Fire Panel is the ideal
solution for small and medium-sized objects. Thanks to
the proven conventional line technology a cost-saving
fire alarm system can be set up.
Three types are available:
FPC‑500‑2: 2 zones for up to 64 detectors
FPC‑500‑4: 4 zones for up to 128 detectors
FPC‑500‑8: 8 zones for up to 256 detectors
With the integrated LCD display, the panel can be
programmed and operated.
The optional extensions such as relay modules, open
collector modules and key switches allow further
tailoring to user needs.
System Overview
Z1…Z8 Up to 8 zones
IN1, IN2 Up to 2 inputs (FPC‑500‑2 and FPC‑500 4 one input)
Two NAC outputs (500 mA each)
ALARM RLY,
FAULT RLY
Alarm and fault relay
AUX AUX power supply (500 mA)
Emergency power supply, up to 2 x 7.2 Ah
1 LEDs
2 LCD display with zone numbers
Vue de la page 0
1 2 3 4 5

Résumé du contenu

Page 1

Fire Alarm Systems | FPC-500 Conventional Fire PanelFPC-500 Conventional Fire Panel www.boschsecurity.com u High-value modern optics – suitable for

Page 2

3 Zone keys and zone status LEDs4 Operating panelFunctionsThe fire panels of FPC-500 series have the followingfeatures available:• Alarm verification•

Page 3

d) The power supply equipment is a pre-assembledpart of the FPC‑500 Conventional Fire Panel. Noadditional commissioning instructions are required.e) T

Page 4

• fuse 5 A @ 60 VDischarge voltagethreshold21.4 VCommunication parametersNACNormal • A- 10 – 15 V• B+ 0 – 0,5 VAlarm • A- 0 – 1 V• B+ 21 – 29 VInput

Page 5 - Represented by:

5 | FPC-500 Conventional Fire PanelRepresented by:© Bosch Security Systems 2012 | Data subject to change without notice1252291339 | en, V3, 21. May 20

Commentaires sur ces manuels

Pas de commentaire